376 WIN-PAK User Guide
2 Individual readers for the panel being configured
are defined on the Reader tab of the SIO Board
Configuration window.
3 Inputs are status points within the system…door
contact inputs, window status inputs, motion
sensors, etc. Panel input points are configured
using the Inputs tab which lists all the input
points available on the current panel.
4 Output points are control points within the
system, such as door locks, parking gates, etc.
5 An ADV must be created for each SIO Board,
and for each input monitor point, output point,
or reader supported by the board.
Refer to "Setting Up Reader Boards" (next section)
for specific procedures to be followed when
configuring a PRO-2200 Intelligent Controller SIO
Board.
The newly defined procedure is shown in the
Procedures list. By expanding the Procedure Actions
tree, you can see a detailed view of each action
defined for this procedure.
Setting Up Reader Boards
The PRO-2200 Series Dual and Single Reader
Modules interface with the Intelligent Controller, to
provide I/O support for card readers. Reader boards
are connected to the PRO-2200 Intelligent
Controller through a supervised RS-485 bus at
38,400 bps.
• The Dual Reader Module provides two Wiegand-
style reader ports, up to eight supervised inputs
and up to six relay outputs.
• The Single Reader Module provides one
Wiegand-style reader port, two supervised inputs
and two relay outputs.
Kommentare zu diesen Handbüchern