356 WIN-PAK User Guide
3 Enter the Controller Address [also known as
the Panel Address]. This corresponds to the DIP
Switch setting on the control panel and falls
within the range of one to eight. See the PRO-
2200 Intelligent Controller Installation Manual
for details.
4 The Host Retry Count is the number of times
the controller will try to make contact with the
panel before sending an alarm indicating it is
offline.
For example, if the Host Retry Count is set to 3
and the DLL receives a bad packet [or does not
get an answer from the Intelligent Controller]
then the DLL will send the packet three more
times.
Host Retry Counts can be set from 2 to 10 [with
3 as the default]. A range of 2 to 4 is recom-
mended for most applications. Retry counts
above 4 would indicate extreme circumstances.
5 The Time to Controller Offline is monitored
and kept within the Intelligent Controller. If the
Intelligent Controller receives neither a poll nor a
message [for example, if it loses communication
with the DLL], it waits the programmed time
then declares that communications with the DLL
have been lost.
The Time to Controller Offline can be set from
10 to 65 seconds [with 15 seconds as the de-
fault]. A range of 10 to 30 seconds is recom-
mended for most applications.
Setup the Panel ADV
6 Set up the default ADV for panel by clicking the
Add button in the ADV area of the window
(upper right corner).